| Approved fluids (other fluids on request) | ||
| Heating water (in accordance with VDI 2035) | • | |
| Water-glycol mixtures (for 20-40 vol.% glycol and fluid temperature ≤ 40 °C) | • | |
| Cooling and cold water | • | |
| Permitted field of application | ||
| Standard version for operating pressure | pmax |
13 bar (up to +140 °C) bar 232 psi (16 bar) up to 248 °F (+120 °C) bar |
| Temperature range at max. ambient temperature +40 °C |
-20...+140 °C (depending on the fluid) |
|
| Max. ambient temperature |
+40 °C |
|
| Installation in closed buildings | • | |
| Pipe connections | ||
| Flange nominal diameter (on the suction side) |
DN 80 |
|
| Flange nominal diameter (on the pressure side) |
DN 65 |
|
| Flanges |
(PN25 on request) |
|
| Flange with pressure-measurement connections |
R 1/8 |
|
| Materials | ||
| Pump volute |
Cast Iron (EN-GJL-250) |
|
| Lantern |
Cast Iron (EN-GJL-250) |
|
| Impeller |
EN-GJL-200 |
|
| Pump shaft |
X39CrMo17-1 (1.4122) |
|
| Mechanical seal |
AQEGG |
|
| Electrical connection | ||
| Nominal speed | n |
2900 rpm |
| Mains connection |
3~400 V, 50 Hz |
|
| Minimum Efficiency Index (MEI) | ||
| Minimum Efficiency Index (MEI) |
≥ 0.40 |
|
| Motor/electronics | ||
| Integrated full motor protection |
Special version with PTC thermistor sensor (KLF) at additional charge |
|
| Protection class |
IP 55 |
|
| Insulation class |
F |
|
| Nominal current (approx.) | IN 3~400 V |
28.5 A |
| Motor efficiency | ηm 50%/ηm 75%/ηm 100% |
88.4/90.2/90.3 % |
| Efficiency | ηM |
0.90 |
| Power factor | cos φ |
0.84 |
| Rated motor power | P2 |
15.0 kW |
| Information for order placements | ||
| Make |
Wilo |
|
| Art no. |
2064877 |
|
| Type |
CronoBloc-BL 65/170-15/2 |
|
| Weight approx. | m |
155 kg |
Observe motor name plate data